In Short
Generator emissions are the pollutants a diesel engine releases, mainly nitrogen oxides and particulates, and they are limited by rules that depend on location, running hours and engine age. EPA Tier 4 in North America and EU Stage V in Europe are the best-known standards, met with exhaust after-treatment where needed.
A diesel engine produces four pollutants that the rules care about: nitrogen oxides (NOx), particulate matter (PM), carbon monoxide (CO) and hydrocarbons (HC). How much of each a generator may emit depends on where it stands, how many hours it runs and when it was built, and the limits have tightened a great deal over the years. This guide explains the pollutants, the main rule families - EPA Tier 4 in North America, EU Stage V in Europe, and the local permits that apply everywhere - and the after-treatment that meets them.
The Pollutants
Nitrogen oxides form at the high temperatures of diesel combustion and are the main concern near people: they contribute to smog and respiratory illness, and most permits limit them first. Particulates are the soot and the ash in the exhaust; the finest particles are the harmful ones and the limits are set by mass and, in the newest rules, by number. Carbon monoxide and hydrocarbons come from incomplete combustion and are the easiest to treat. Carbon dioxide is not a pollutant in this sense but a fuel-consumption figure; fuels such as HVO reduce it without changing the engine.
The Rule Families
In the United States the EPA regulates the engines of non-road and stationary sets by tiers: Tier 4 Final, the current standard for most sizes, cuts NOx and PM drastically and in practice requires after-treatment on larger engines. Emergency standby sets have had an exemption with a running-hour limit; sets that run for grid support or more than the permitted hours must meet the full standard. In the European Union, Stage V applies to non-road mobile machinery including mobile generators; stationary sets fall under the Medium Combustion Plant Directive and national permits, with limits by size and running hours. Elsewhere the rules often follow one of these two families or set their own, and the local permit of the site is always the one that counts.
The rule depends on the set's classification - emergency, standby, prime, mobile - the engine size, the running hours and the date of installation, and the enquiry should state which permit the site holds or applies for.
After-Treatment: SCR, Catalysts and Filters
Selective catalytic reduction (SCR) is the main NOx measure: a urea solution is dosed into the exhaust, decomposes to ammonia and reacts with the NOx on a catalyst to nitrogen and water, removing most of it. It needs a dosing system, a urea tank, enough exhaust heat and a control that follows the engine load. A diesel oxidation catalyst (DOC) burns CO and HC and is often placed before the SCR; a diesel particulate filter (DPF) traps the soot and regenerates it by burning, which requires exhaust temperature or an active system. Modern engines combine these with internal measures - high-pressure injection, exhaust gas recirculation, timing - and the maker certifies the engine with its after-treatment as one system.
All after-treatment adds back pressure, weight, length and heat, and it must fit into the exhaust system and the enclosure: the SCR reactor and the urea tank take space, the pipework between engine and catalyst must keep the gas hot, and the whole chain is checked against the engine maker's back pressure limit.
What It Means for the Package
An emissions requirement changes the generator package: the exhaust system grows into a reactor with dosing, the enclosure or container gets longer or a roof-mounted reactor, the urea supply becomes part of the fuel logistics, and the testing includes the after-treatment's performance. AXON builds exhaust and SCR systems, oxidation catalysts and particulate filters into its containers and enclosures for generator sets of any make, matched to the engine and the limit the permit sets, together with the silencers and the stack.
In short
- NOx, PM, CO and HC are regulated; NOx first near people
- EPA Tier 4 in North America, EU Stage V and the MCP Directive in Europe, local permits everywhere
- Emergency sets have running-hour exemptions; grid support and long running do not
- SCR removes most of the NOx; DOC handles CO and HC; DPF traps particulates
- After-treatment adds back pressure, space, urea logistics and testing
- AXON integrates SCR, catalysts, filters, silencers and stacks into its packages
What to send with an enquiry
- The emissions rule or permit the site falls under, with its limits
- Classification of the set: emergency, standby, prime, mobile, and the running hours
- Engine make, model, exhaust flow, temperature and its own emissions data
- Sound limit, because the silencer and the reactor are planned together
- Space for the reactor and the urea tank, inside or on the roof
- Fuel: diesel or HVO, and the sulphur content
Questions we are often asked
Does a standby generator need SCR?
Depends on the permit: many emergency-only sets with limited running hours are exempt, while sets near populated areas, in strict jurisdictions or with grid-support running must meet NOx limits that only SCR reaches. The local authority decides.
What is Tier 4 Final?
The current EPA standard for non-road diesel engines: NOx and PM limits so low that larger engines use SCR and filters to meet them. Stationary sets follow related EPA rules with their own categories.
What is Stage V?
The EU standard for non-road mobile machinery engines, including mobile generator sets, with limits on NOx, PM mass and particle number. Stationary sets in the EU follow the Medium Combustion Plant Directive and national rules instead.
How much urea does an SCR use?
A modest amount compared with the fuel. The urea tank has to cover the running hours between refills and must be kept from freezing.
Can an existing set be retrofitted with SCR?
Often yes: an SCR reactor, dosing system and controls are added to the exhaust line, matched to the engine. The back pressure, the space and the exhaust temperature decide whether it is practical.
Products
- Exhaust Gas System with SCR
- Generator Exhaust Silencers and Mufflers
- Containers for Power Generators
- Air Outlet Chimney
Further reading
- Data Center Generator Emissions and Noise: SCR, Silencers and Acoustic Enclosures
- Exhaust Back Pressure: Why the Silencer and the Pipe Route Decide Generator Output
- Exhaust and SCR Systems for Generator Sets
- Diesel Generator Exhaust System Components: Silencer, SCR, Pipework
- Data Center Backup Generator Requirements: Ratings, Redundancy, Fuel, Noise and Emissions